MV Capacitors Bank Failures and Neutral Unbalance Current

Capacitors Bank Applications

Capacitor Banks installed in factories and substation for many reasons like

  • Power Factor correction and compensating Load Inductive Reactive Power and this will help to utilize the rated power of the substation power equipment like, transformers, cables, switch gears, … etc to carry more active power instead of inductive reactive power.
  • Enhance the system voltage.
  • Filter harmonics generated by the nonlinear loads.
Capacitor Bank Components

MV Capacitors Bank Connections Diagram

In Medium Voltage Networks, Most Common Capacitors Bank Configuration will be Y-Y Double Floating Neutral Stars with Neutral Unbalance Current transformer NCT

  • Floating Neutral will prevent Capacitors from participating in External L-G Faults.
  • CT between both Neutral points to help 60N Protection function to detect the neutral unbalance current due to any capacitor unit failure.
Capacitor Bank Protection Functions

Real Fault Disturbance Record for Capacitor Unit Fuse Failure

Membership Required

This content is available to VIP members only.

Sign up to unlock access or log in if you already have an account.

Log In

Simulating Capacitors Bank in healthy condition

This is 132/13.8KV Substation, and we have 7MVAR Capacitors Bank in Y-Y configuration
Each Y have 2 capacitor units, so the phase will have 4 capacitor units.
We can see the Capacitors bank #1 loading current 290A with almost Zero Neutral Unbalance Current and Zero Neutral Voltage.

MATLAB SIMULINK Simulation Model Component

Membership Required

This content is available to VIP members only.

Sign up to unlock access or log in if you already have an account.

Log In

Simulating Capacitor Unit Fuse Failure

We will disconnect one capacitor unit to simulate one unit fuse failure

  • R phase current dropped to 234.8A
  • Neutral Unbalance current increased to 39A
  • Neutral Voltage increased to 1232V

MATLAB SIMULINK Simulation Model Component

Membership Required

This content is available to VIP members only.

Sign up to unlock access or log in if you already have an account.

Log In

Simulating Capacitor Branch Fuse Failure

We will disconnect two capacitor unit to simulate branch failure

  • R phase current dropped to 169A
  • Neutral Unbalance current increased to 84.6A
  • Neutral Voltage increased to 2678V

MATLAB SIMULINK Simulation Model Component

Membership Required

This content is available to VIP members only.

Sign up to unlock access or log in if you already have an account.

Log In

Simulating Capacitor Phase Lost

We will disconnect complete phase to simulate broken phase or Circuit Breaker pole failed to close

  • R phase current dropped to Zero A
  • Neutral Unbalance current Not Available as both Star neutral points will have the same voltage as both star have the same failure condition
  • Neutral Voltage increased to 6573 V

MATLAB SIMULINK Simulation Model Component

Membership Required

This content is available to VIP members only.

Sign up to unlock access or log in if you already have an account.

Log In

Quiz with Answers

MV Capacitors Bank Failures and Neutral Unbalance Current Post Quiz